Power Fittings & Cable Accessories

Products

Explore power fittings and cable accessories for transmission, distribution and communication networks. Browse the categories or send us your product requirements.

Power Fittings & Cable Accessories

Drop Type Fuse Cutout

Drop type fuse cutouts are outdoor high voltage protection facilities. The fuse is installed at high voltage side of transformer or branch line of distribution line to protect transformer or transmission line from short circuit and overload, to break and connect load current. Fuse cutout consist of insulation bracket and fuse tube, fixed contact is…

Product Details

Drop type fuse cutouts are outdoor high voltage protection facilities. The fuse is installed at high voltage side of transformer or branch line of distribution line to protect transformer or transmission line from short circuit and overload, to break and connect load current.

Fuse cutout consist of insulation bracket and fuse tube, fixed contact is installed at both ends of insulation bracket, moving contact is installed at both ends of fuse tube. Fuse tube consist of two parts, arcing extinguish tube in inner side and epoxy glass tube outside. Tension load fuse cutout increase the flexible auxiliary contact and arcing-extinguish shield to break or connect load current.

Drop type fuse cutout is a low cost line protection, primarily used on remote overhead electrical transmission lines. The visual display of the status of the fuse cutout quickly and accurately helps field inspectors to locate the faulty segment of the overhead transmission line. Upon clearing of the line fault and replacing the fuse link, each of the phases can then be individually switched back into operation using operating poles, which are available in desired lengths.

1、Service condition:

a) The ambient air temperatures: -40 to 40℃

b) The altitude above sea level: 1000m.

c) Wind speed doesn’t exceed 700Pa (not exceed 34m/s)

d) The earthquake intensity doesn’t exceed 8 degrees.

2、The product is not applicable to the following locations:

a) Combustion or explosion risk areas.

b) With severe vibration or shock sites.

c) A conductive, chemical gas and serious pollution, salt fog area.

图片1.png

Fuse Cutout Series 12-36kV

11-15kV

Item No. Rated Voltage (kV) Rated Current (A) Breaking Current (A) Impulse Voltage (BIL) Power Frequency Withstand Voltage Leakage Distance (MM) Weight (KG) Dimension (CM)
YJF-1 12 100 6300 110 40 250 6.5 40×36×11.5
YJF-1 12 200 10000 110 40 250 6.5

11-15kV

Item No. Rated Voltage (kV) Rated Current (A) Breaking Current (A) Impulse Voltage (BIL) Power Frequency Withstand Voltage Leakage Distance (MM) Weight (KG) Dimension (CM)
YJF-2 15 100 8000 125 45 320 7.5 50×36×12.5
YJF-2 15 200 12500 125 45 320 7.5

11- 15KV( F)

Item No. Rated Voltage (kV) Rated Current (A) Breaking Current (A) Impulse Voltage (BIL) Power Frequency Withstand Voltage Leakage Distance (MM) Weight (KG) Dimension (CM)
YJF2(F)-2 15 100 8000 125 45 320 8 58×40×15
YJF2(F)-2 15 200 12500 125 45 320 8

24kV-27kV

Item No. Rated Voltage (kV) Rated Current (A) Breaking Current (A) Impulse Voltage (BIL) Power Frequency Withstand Voltage Leakage Distance (MM) Weight (KG) Dimension (CM)
YJF-3 24 100 8000 150 65 530 12 50×38×16
YJF-3 24 200 12500 150 65 530 12

图片2.png

Fuse Cutout Series 12-36kV

33kV-36kV

Item No. Rated Voltage (kV) Rated Current (A) Breaking Current (A) Impulse Voltage (BIL) Power Frequency Withstand Voltage Leakage Distance (MM) Weight (KG) Dimension (CM)
YJF-4 33 100 8000 170 70 720 15 64×35×18
YJF-4 33 200 12500 170 70 720 15

11kV-15kV

Item No. Rated Voltage (kV) Rated Current (A) Breaking Current (A) Impulse Voltage (BIL) Power Frequency Withstand Voltage Leakage Distance (MM) Weight (KG) Dimension (CM)
YJF-5 12 100 6300 110 40 250 6.5 40×36×11.5
YJF-5 12 200 10000 110 40 250 6.5

24kV-27kV

Item No. Rated Voltage (kV) Rated Current (A) Breaking Current (A) Impulse Voltage (BIL) Power Frequency Withstand Voltage Leakage Distance (MM) Weight (KG) Dimension (CM)
YJF-6 24 100 8000 150 65 540 10 60×38×16
YJF-6 24 200 12500 150 65 540 10

11- 15KV

Item No. Rated Voltage (kV) Rated Current (A) Breaking Current (A) Impulse Voltage (BIL) Power Frequency Withstand Voltage Leakage Distance (MM) Weight (KG) Dimension (CM)
HYJF-2 15 100 6300 110 40 250 6 40×36×11.5
HYJF-2 15 200 10000 110 40 250 6

图片3.png

Fuse Cutout Series 12-36kV

11- 15KV

Item No. Rated Voltage (kV) Rated Current (A) Breaking Current (A) Impulse Voltage (BIL) Power Frequency Withstand Voltage Leakage Distance (MM) Weight (KG) Dimension (CM)
HYJF-2 15 100 6300 110 40 250 6 40×38×16
HYJF-2 15 200 10000 110 40 250 6

24-27kV

Item No. Rated Voltage (kV) Rated Current (A) Breaking Current (A) Impulse Voltage (BIL) Power Frequency Withstand Voltage Leakage Distance (MM) Weight (KG) Dimension (CM)
HYJF-3 24 100 8000 150 65 530 7 50×38×16
HYJF-3 24 200 12500 150 65 530 7

33-36kV

Item No. Rated Voltage (kV) Rated Current (A) Breaking Current (A) Impulse Voltage (BIL) Power Frequency Withstand Voltage Leakage Distance (MM) Weight (KG) Dimension (CM)
HYJF-4 33 100 8000 125 45 320 7.5 50×38×12.5
HYJF-4 33 200 12500 125 45 320 7.5

24kV-27kV

Item No. Rated Voltage (kV) Rated Current (A) Breaking Current (A) Impulse Voltage (BIL) Power Frequency Withstand Voltage Leakage Distance (MM) Weight (KG) Dimension (CM)
HYJF-3 24 100 8000 150 65 540 7 50×38×16
HYJF-3 24 200 12500 150 65 540 7

图片4.png

33-36kV

Item No. Rated Voltage (kV) Rated Current (A) Breaking Current (A) Impulse Voltage (BIL) Power Frequency Withstand Voltage Leakage Distance (MM) Weight (KG) Dimension (CM)
HYJF-4 33 100 8000 170 70 720 8 64×36×18
HYJF-4 33 200 12500 170 70 720 8

24kV-27kV

Item No. Rated Voltage (kV) Rated Current (A) Breaking Current (A) Impulse Voltage (BIL) Power Frequency Withstand Voltage Leakage Distance (MM) Weight (KG) Dimension (CM)
HYJF-7 24 100 8000 150 65 540 10 50×36×16
HYJF-7 24 200 10000 150 65 540 10

33kV-36kV

Item No. Rated Voltage (kV) Rated Current (A) Breaking Current (A) Impulse Voltage (BIL) Power Frequency Withstand Voltage Leakage Distance (MM) Weight (KG) Dimension (CM)
HYJF-8 33 100 10000 170 70 720 15 64×35×18
HYJF-8 33 200 12500 170 70 720 15

12kV

Item No. Rated Voltage (kV) Rated Current (A) Breaking Current (A) Impulse Voltage (BIL) Power Frequency Withstand Voltage Leakage Distance (MM) Weight (KG) Dimension (CM)
RW11 12 100 6300 110 42 260 7.5 48×32×27
RW11 12 200 8000 110 42 260 7.5

图片5.png

Related Products

Need details about this product?