Power Fittings & Cable Accessories
Heat Shrink Bus-bar Insulation Tubing
Application Used in medium voltage substations up to 36kV to reduce electric clearance and increase insulation between bus-bars Feature 1.Anti-tracking 2.Excellent corrosion resistance 3.UV resistance and weathering resistance 4.Superior electrical and mechanical properties performance. Performance
Product Details
Application
Used in medium voltage substations up to 36kV to reduce electric clearance and increase insulation between bus-bars
Feature
1.Anti-tracking
2.Excellent corrosion resistance
3.UV resistance and weathering resistance
4.Superior electrical and mechanical properties performance.

Performance
| Test | Test Method | Requirement |
| Tensile strength | ASTM D 2671 | ≥11.8MPa |
| Elongation at break | ASTM D 2671 | 700% |
| tensile strength after heat aging | ASTM D 2671/120℃,168小h | ≥10MPa |
| Elongation at break after heat aging | ASTM D 2671/120℃,168h | ≥500% |
| Longitudinal shrinkage | ASTM D 2671 | 0 to-10% |
| Electrical strength | IEC 243 | ≥20KV/mm |
| Dielectric constant | IEC 250 | 3.0 Max |
| Volume resistivity | IEC 93 | 1013Ω.cm |
| Flame retardancy (oxygen index) | ASTM 4589 | ≥25 |
| Copper corrosive 120 ° C, 168 hours | ASTM D 2671 | Pass |
| Low temperature brittleness -40 ° C, 4 hours | ASTM D 2671 | No crack |
| Water absorption rate | ISO 62/23℃,14 days | ≤0.5% |