GN19-12(C) Indoor High Voltage Isolate Switch

GN19- 12(C) indoor disconnecting switch is applied in power system with rated voltage 12kV, AC 50Hz and below, it uses with CS6-1 manual operating mechanism, for making and breaking the circuit with voltage and without load, it has pollution proof type, plateau type and adding electrification indication type. Definition of model Add power display device…

Product Details

GN19- 12(C) indoor disconnecting switch is applied in power system with rated voltage 12kV, AC 50Hz and below, it uses with CS6-1 manual operating mechanism, for making and breaking the circuit with voltage and without load, it has pollution proof type, plateau type and adding electrification indication type.

Definition of model

Add power display device

G- Plateaux type W-Antifouling type

Rated current

Wall type: C1-turn at the side of wall

C2-break at the side of wall

C3-Both sides at the side of wall

Rated voltage

Design number

Indoor type

Isolate switch

Service condition

1.The altitude above sea level: 2000m.

2.The ambient air temperatures: -40 to 40℃.

3.Wind speed doesn’t exceed 700Pa (not exceed 34m/s).

4.The earthquake intensity doesn’t exceed 8 degrees.

5.The working situation: without frequent violent vibration.

6.The installation site of ordinary type isolator should be kept away from gas, smoke chemical deposition, salt-spray fog, dust and other explosive and corrosive maters that affect seriously insulation and conduction capability of the isolator.

7.Pollution proof type isolator applies to sever filthy conduction area. However, it shouldn’t be any explosive matters and matters causing fire.

GN19-12(C) Indoor High Voltage Isolate SwitchGN19-12(C) Indoor High Voltage Isolate Switch

GN19-12(C) Indoor High Voltage Isolate Switch

G19 Key Technical Parameters

Items Units Technical parameters
Rated voltage kV 12-15
1 min Power frequency withstand voltage To earth kV 38
Across open DS kV 42
Lightning impulse withstand voltage To earth kV 75
Across open DS kV 85
Rated frequency Hz 50
Rated current A 200、400/630/1000/1250
Short time withstand current(4s) kA 6.3/12.5/20/31.5/40
Rated peak withstand current kA 16/31.5/50/80/100
Rated duration of short/circuit S 4/2
Creepage Distance mm 300-380
Mechanical life times 2000
Type Rated Voltage(kV) Rated Current(A) Short time withstand current(4s) kV Rated peak withstand current kV
GN119-12/400-12.5 12 400 12.5 31.5
GN19-12/630-20 12 630 20 50
GN19-12/1000-31.5 12 1000 31.5 80
GN19-12/1250-31.5 12 1250 31.5 80
GN19-12/400-12.5 12 400 12.5 31.5
GN19-12/630-20 12 630 20 50
GN19-12/1000-31.5 12 1000 31.5 80
GN19-12/1250-31.5 12 1250 31.5 80