Medium Voltage Heat Shrinkable Termination& Straight Joint Accessories

Heat shrinkable termination & straight joint accessories are suitable for up to 11/20/35kV, insulated with PVC,XLPE and PE polymeric cables. Feature 1.Reliable stress control 2.Large cross-section range 3.Excellent corrosion resistance 4.UV resistance and weathering resistance 5.Anti-tracking 6.Superior electrical and mechanical properties 7.Easy installation Performance of 11KV Performance of 20KV Performance of 35KV

Product Details

Heat shrinkable termination & straight joint accessories are suitable for up to 11/20/35kV, insulated with PVC,XLPE and PE polymeric cables.

Feature

1.Reliable stress control

2.Large cross-section range

3.Excellent corrosion resistance

4.UV resistance and weathering resistance

5.Anti-tracking

6.Superior electrical and mechanical properties

7.Easy installation

1591856740142984.jpg

Performance of 11KV

Test Requirement
Power frequency withstand voltage 1min 45kV,No flashover, no breakdown
Partial discharge ≤10PC at 13kV
Heating cycles in air 22kV.Heating cycle at least 8h, 95℃-100℃ at least 2h, natural cooling at least 3h, total 60 heating cycles
Impluse voltage (peak) 105kV,No flashover, no breakdown
Negative DC voltage 15 min 52kV, No flashover, no breakdown
Power frequency withstand voltage 4h 35kV, No flashover, no breakdown

Performance of 20KV

Test Requirement
Power frequency withstand voltage 1min 75kV,No flashover, no breakdown
Partial discharge ≤10PC at 27kV
Heating cycles in air 45kV.Heating cycle at least 8h, 95℃-100℃ at least 2h, natural cooling at least 3h, total 60 heating cycles
Impluse voltage (peak) 170kV,No flashover, no breakdown
Negative DC voltage 15 min 108kV, No flashover, no breakdown
Power frequency withstand voltage 4h 72kV, No flashover, no breakdown

Performance of 35KV

Test Requirement
Indoor moisture 32.5kV,300h,No flashover, no breakdown
Outdoor salt fog 32.5kV,1000h,No flashover, no breakdown
Partial discharge ≤10PC at 45kV
Heating cycles in air 65kV.Heating cycle at least 8h, 95℃-100℃ at least 2h, natural cooling at least 3h, total 60 heating cycles
AC voltage withstand 1min 104kV, No flashover, no breakdown
DC voltage withstand 15min 104kV, No flashover, no breakdown
AC voltage withstand 5min 117kV, No flashover, no breakdown
Impluse voltage (peak) 200kV,No flashover, no breakdown